Title of article :
Seismic reliability of electrical power transmission systems Original Research Article
Author/Authors :
J.A. Pires، نويسنده , , A.H.-S. Ang، نويسنده , , R. Villaverde، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
13
From page :
427
To page :
439
Abstract :
The reliability of electric power transmission systems is important for the probabilistic safety assessment of nuclear power plants under a given earthquake loading as it relates to the loss of off site power to the nuclear power plants. Here, a comprehensive model to evaluate the seismic reliability of electric power transmission systems is presented. The model provides probabilistic assessments of structural damage and abnormal power flow that can lead to power interruption in a transmission system under a given earthquake. With the proposed methodology seismic capacities of electrical. equipment are determined on the basis of available test data and simple modeling from which fragility functions of specific substations are developed. Earthquake ground motions are defined as stochastic processes. Probabilities of network disconnectivity and abnormal power flow are assessed through Monte Carlo simulations. The proposed model is applied to the electric power network in San Francisco and vicinity under the 1989 Loma Prieta earthquake, and the probabilities of power interruption are contrasted with the actual power failures observed during that earthquake.
Journal title :
Nuclear Engineering and Design Eslah
Serial Year :
1996
Journal title :
Nuclear Engineering and Design Eslah
Record number :
888001
Link To Document :
بازگشت