Title of article :
Avoiding sustained oscillations in power systems with tap changing transformers
Author/Authors :
Hill، D. J. نويسنده , , Wu، Q. نويسنده , , Popovic، D. H. نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
The problem of avoiding sustained oscillations in power systems with dynamic loads and tap changing transformers is analyzed. Deadband size adjustment is used to eliminate limit cycles which originate from tap-load interactions. The analysis demonstrates the role of load dynamics in providing a deadband setting which guarantees the absence of sustained oscillatory behavior.
Keywords :
Coal-fired generation , Base load , Mid-merit position
Journal title :
INTERNATIONAL JOURNAL OF ELECTRLCAL POWER & ENERGY
Journal title :