Author/Authors :
William S. Duff a، نويسنده , , *، نويسنده , , Roland Winston b، نويسنده , , Joseph J. O’Gallagher b، نويسنده , ,
James Bergquam c، نويسنده , , Thomas Henkel، نويسنده ,
Abstract :
In 1998 two new technologies were demonstrated for the first time in a commercial building: (1) a new integrated
CPC reflector evacuated solar collector (ICPC) and (2) the solar operation of a double effect absorption (2E) chiller.
The 106.5 m2 ICPC collector array consisted of 336 evacuated tubes. A commercial 2E gas-fired absorption chiller was
modified to operate with 150 C hot water from the solar collector array. Daily collection efficiencies of nearly 50% and
instantaneous collection efficiencies of about 60% were achieved throughout the first two years of operation. Daily
chiller COPs of about 1.1 were also achieved.
2003 Elsevier Ltd. All rights reserved.