Title of article :
An exergy analysis of a solar-driven ejector refrigeration system
Author/Authors :
Wimolsiri Pridasawas *، نويسنده , , Per Lundqvist، نويسنده ,
Issue Information :
دوماهنامه با شماره پیاپی سال 2004
Pages :
11
From page :
369
To page :
379
Abstract :
Exergy analysis is used as a tool to analyse the performance of an ejector refrigeration cycle driven by solar energy. The analysis is based on the following conditions: a solar radiation of 700 W/m2, an evaporator temperature of 10 C, a cooling capacity of 5 kW, butane as the refrigerant in the refrigeration cycle and ambient temperature of 30 C as the reference temperature. Irreversibilities occur among components and depend on the operating temperatures. The most significant losses in the system are in the solar collector and the ejector. The latter decreases inversely proportional to the evaporation temperature and dominates the total losses within the system. The optimum generating temperature for a specific evaporation temperature is obtained when the total losses in the system are minimized. For the above operating conditions, the optimum generating temperature is about 80 C. 2003 Elsevier Ltd. All rights reserved.
Keywords :
Solar cooling , Ejector , Exergy
Journal title :
Solar Energy
Serial Year :
2004
Journal title :
Solar Energy
Record number :
939295