Title of article :
A study on the design and analysis of a heat pump heating
system using wastewater as a heat source
Author/Authors :
N.C. Baek a، نويسنده , , *، نويسنده , , U.C. Shin b، نويسنده , , J.H. Yoon، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2005
Abstract :
In this study, the compression heat pump system using wastewater, as a heat source, from hotel with sauna was
designed and analyzed. This study was performed to investigate the feasibility of the wastewater use for heat pump
as a heat source and to obtain engineering data for system design. This heat pump system uses off-peak electricity that
is a cheap energy compared to fossil fuel in Korea. For this, the charging process of heat into the hot water storage tank
is achieved only at night time (22:00–08:00). TRNSYS was used for the system simulation with some new components
like the heat pump, which we create ourselves.
As a result, it was forecasted that the yearly mean COP of heat pump is about 4.8 and heat pump can supply 100% of
hot water load except weekend of winter season. The important thing that should be considered for the system design is
to decrease the temperature difference between condenser and evaporator working fluids during the heat charging process
by the heat pump. This heat pump system using wastewater from sauna, public bath, building, etc. can therefore be
effectively applied not only for water heating but also space heating and cooling in regions like as Korea.
2004 Elsevier Ltd. All rights reserved.
Keywords :
Hot water heating , Wastewater , TRNSYS , Off-peak electricity , Heat pump
Journal title :
Solar Energy
Journal title :
Solar Energy