Title of article
Simplified analysis of coupled heat and mass transfer processes in packed bed liquid desiccant-air contact system
Author/Authors
Ren Chengqin، نويسنده , , b، نويسنده , , *، نويسنده , , JIANG YI HONG، نويسنده , , Zhang Yianpin b، نويسنده ,
Issue Information
ماهنامه با شماره پیاپی سال 2006
Pages
11
From page
121
To page
131
Abstract
One-dimensional model is frequently used to describe the coupled heat and mass transfer processes in the packed bed
liquid desiccant dehumidifier/regenerator. In this paper, within relatively narrow range of operating conditions which
are usually encountered in practical dehumidification/regeneration processes, the linear approximation was made to
find out the dependence of equilibrium humidity ratio on solution temperature. New parameters were defined and
the original equations were rearranged to obtain two coupled ordinary differential equations. For the general cases with
different values of Lewis factor, approximations of constant properties and coefficients were further made to render the
coupled equations linear. Roots of the characteristic equation were determined algebraically and analytical solution to
the linear coupled equations was obtained. Analytical expression for the tower efficiency was further developed based
on the analytical solution. The way for obtaining the averaged overall heat and mass transfer coefficients from experimental
data in a coupled heat and mass transfer manner was finally indicated. Coefficients obtained in this manner
can be used in finite difference model to produce more accurate outlet conditions.
2005 Elsevier Ltd. All rights reserved.
Keywords
Packed bed dehumidification/regeneration , coupled heat and mass transfer , Analytical solution , Tower efficiency1. IntroductionLiquid desiccant cooling system driven by solar energyor other heat sources was emerged as a potentialalternative or
Journal title
Solar Energy
Serial Year
2006
Journal title
Solar Energy
Record number
939575
Link To Document