Title of article :
Energy optimization of air conditioning system
using hydrosolar roof as a heat sink
Author/Authors :
M. Lucas a، نويسنده , , *، نويسنده , , A.S. Kaiser b، نويسنده , , A. Viedma، نويسنده , , B. Zamora b، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2006
Abstract :
An environmentally friendly alternative device, called hydrosolar roof, designed for heat dissipation in buildings has
been integrated into a standard air conditioning system. To perform an energy consumption optimization it has been
necessary to include all the elements in a global model. Then, three main subsystems have been considered: cooling
machine, hydraulic network and hydrosolar roof. A description of the three subsystems is done and the mathematical
model is presented. The cooling machine thermodynamic model has been carried out using EES (engineering equation
solver). The hydraulic network model has piping, pump and nozzle information. The hydrosolar roof direct contact
heat and mass transfer simulation has been developed with a CFD code. Special attention has been paid on the cooling
efficiency. The global model has been applied to a real prototype facility experimentally tested. All the energy consumptions
have been calculated for different pumping heads. A global coefficient of performance (COP) has been defined and
the optimum value obtained.
2005 Elsevier Ltd. All rights reserved
Keywords :
Air conditioning , Cooling tower , drop size , Solar chimney , Solar energy
Journal title :
Solar Energy
Journal title :
Solar Energy