Title of article :
Experimental investigations on solar chimney for room ventilation
Author/Authors :
Jyotirmay Mathur، نويسنده , , *، نويسنده , , N.K. Bansal، نويسنده , , Sanjay Mathur، نويسنده , , Meenakshi Jain، نويسنده , , Anupma a، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2006
Pages :
9
From page :
927
To page :
935
Abstract :
Experimental investigations on a small size solar chimney show that the rate of ventilation increases with increase of the ratio between height of absorber and gap between glass and absorber. This finding is in agreement with results of the steady-state mathematical model developed for analysis of such systems. Nine different combination of absorber height and air gap have been investigated on the experimental set-up. Highest rate of ventilation induced with the help of solar energy was found to be 5.6 air change per hour in a room of 27 m3, at solar radiation 700 W/m2 on vertical surface with the stack height-air gap ratio of 2.83 for a 1 m high chimney. 2005 Elsevier Ltd. All rights reserved
Keywords :
Solar chimney , Air movement , Stack effect , Natural ventilation
Journal title :
Solar Energy
Serial Year :
2006
Journal title :
Solar Energy
Record number :
939660
Link To Document :
بازگشت