Title of article :
Energy efficient office buildings with passive cooling – Results
and experiences from a research and demonstration programme
Author/Authors :
Karsten Voss، نويسنده , , *، نويسنده , , Sebastian Herkel، نويسنده , , Jens Pfafferott، نويسنده , ,
Gu¨nter Lo¨hnert c، نويسنده , , Andreas Wagner، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2007
Abstract :
To gain access to information on energy use in office buildings, the German Federal Ministry for Economy launched an intensive
research and demonstration programme in 1995. In advance of the 2002 EU energy performance directive a limited primary energy coefficient
of about 100 kW h m 2 a 1 as a goal for the complete building services technology was postulated (HVAC + lighting) for all demonstration
buildings to be supported. A further condition was that active cooling be avoided. Techniques such as natural or mechanical
night ventilation or heat removal by slab cooling with vertical ground pipes as well as earth-to-air heat exchangers in the ventilation
system were applied. An accompanying research was established to keep track of the results and the lessons learned from about 22 demonstration
buildings realized and monitored until the end of 2005. As one outcome this paper summarises the energy performance of a
selection of characteristic buildings together with an overview on the summer thermal comfort situations achieved. The research program
will proceed during the next five years. Detailed reports and future results may be downloaded from the internet: www.enbaumonitor.
de.
2006 Elsevier Ltd. All rights reserved.
Keywords :
Office buildings , user behaviour , Passive cooling , Thermal comfort , Energy monitoring