Title of article :
Research on ratio selection of a mixed liquid desiccant: Mixed LiCl–CaCl2 solution
Author/Authors :
Xiu-Wei Li *، نويسنده , , Xiao-Song Zhang، نويسنده , , Geng Wang، نويسنده , , Rong-Quan Cao، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2008
Pages :
11
From page :
1161
To page :
1171
Abstract :
Liquid desiccant cooling system is a new type of air-conditioning system capable of saving energy. The dehumidification process dominates the performance of this system, while the thermal properties of the liquid desiccant play a key role in improving dehumidification effect. However, there is little work about how to choose a proper liquid desiccant that has a better performance. To settle this problem, a novel method is proposed to search an ideal liquid desiccant by applying the nonrandom two-liquid equation (NRTL equation). This idea is further applied to mixed LiCl and CaCl2 solution to work out the right mixture ratio with a better dehumidification effect under certain working conditions. Moreover, the related experiments were carried out. The results show that: compared to single LiCl solution, the dehumidification effect could be raised by more than 20% with mixed LiCl and CaCl2 solution. 2008 Elsevier Ltd. All rights reserved
Keywords :
Mixed liquid desiccant , Dehumidification effect , Liquid-dehumidification , activity coefficient
Journal title :
Solar Energy
Serial Year :
2008
Journal title :
Solar Energy
Record number :
939993
Link To Document :
بازگشت