Title of article :
Very low temperature radiant heating/cooling indoor end system
for efficient use of renewable energies
Author/Authors :
Jianbo Ren، نويسنده , , Li Zhu b، نويسنده , , *، نويسنده , , Yiping Wang، نويسنده , , Congrong Wang a، نويسنده , , Weicheng Xiong a، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2010
Abstract :
Solar or solar-assisted space heating systems are becoming more and more popular. The solar energy utilization efficiency is high when
the collector is coupled with indoor radiant heating suppliers, since in principle, lower supply temperature means lower demand temperature
and then the system heat loss is less. A new type radiant end system is put forward for even lower supply temperature compared to
the conventional radiant floor heating systems. A three dimensional model was established to investigate its energy supply capacities.
Simulation results show that 50W per meter length tube can be achieved with the medium temperature of 30 C for heating and
15 C for cooling. The predicted results agree well with the actual data from a demonstration building. Furthermore, it is demonstrated
that a supply temperature of 22 C in winter and of 17 C in summer already met the indoor requirements. The new end system has good
prospects for effective use of local renewable resources.
2010 Elsevier Ltd. All rights reserved
Keywords :
Solar heating , Nocturnal cooling , computational simulation , Radiant floor heating , Space heating and cooling