Title of article :
Solar absorption cooling plant in Seville
Author/Authors :
Pablo Bermejo *، نويسنده , , Francisco Javier Pino، نويسنده , , Felipe Rosa، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2010
Abstract :
A solar/gas cooling plant at the Engineering School of Seville (Spain) was tested during the period 2008–2009. The system is composed
of a double-effect LiBr + water absorption chiller of 174 kW nominal cooling capacity, powered by: (1) a pressurized hot water
flow delivered by mean of a 352 m2 solar field of a linear concentrating Fresnel collector and (2) a direct-fired natural gas burner. The
objective of the project is to indentify design improvements for future plants and to serve as a guideline. We focused our attention on the
solar collector size and dirtiness, climatology, piping heat losses, operation control and coupling between solar collector and chiller. The
daily average Fresnel collector efficiency was 0.35 with a maximum of 0.4. The absorption chiller operated with a daily average coefficient
of performance of 1.1–1.25, where the solar energy represented the 75% of generator’s total heat input, and the solar cooling ratio (quotient
between useful cooling and insolation incident on the solar field) was 0.44.
2010 Elsevier Ltd. All rights reserved
Keywords :
Solar cooling , Double-effect absorption chiller , Linear Fresnel solar collector , Solar cooling ratio , Solar heat fraction