• Title of article

    Turbulent heat transfer and flow characteristics in a horizontal circular tube with strip-type inserts. Part I. Fluid mechanics

  • Author/Authors

    Hsieh، Shou-Shing نويسنده , , Wu، Feng-Yu نويسنده , , Tsai، Huang-Hsiu نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    -822
  • From page
    823
  • To page
    0
  • Abstract
    This paper is the first of two papers that present the result of a study of turbulent flow and pressure drop in a horizontal tube with strip type inserts. Experimental data taken for air for a class of strip type inserts (longitudinal, LS and cross, CS inserts) used as a tube side heat transfer augmentative device for a singlephase cooling mode operation are presented. To broaden the understanding of the underlying physical phenomena responsible for the heat transfer enhancement, flow mechanisms through velocity measurements are combined with pressure drop measurements to develop friction factor correlations for 6500<=Re<=19 500 where Re is the Reynolds number. Friction factor increases were typically between 1.1 and 1.5 from low Re(~=6500) to high Re(~=19 500) with respect to bare tubes.
  • Keywords
    Reflectance measurements , corn , Nitrogen deficiency , Crop N monitoring
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2003
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Record number

    96117