Title of article :
Reduction of fine airborne particulates žPM / in a small 3
city centre office, by altering electrostatic forces
Author/Authors :
G. Richardsona، نويسنده , , D.J. Harwooda، نويسنده , , S.A. Eickb، نويسنده , , F. Dobbsc، نويسنده , , K.G. Ros´end، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
A two stage intervention study was carried out to establish the degree to which a newly developed, electrostatic air
cleaning ŽEAC. system can improve indoor air quality ŽIAQ. by reducing the number of airborne fine particles. The
IAQ and how employees in a city centre office Ž49 m2. perceived it, was monitored from May until November 1998.
The number of fine particles, PM3 Ž0.3 3.0 m.; number of coarse particles, PM7 Ž3.0 7.0 m.; number of small
positive and negative air ions; relative humidity and temperature were recorded in and out of doors. To assess the
employees’ perception of any changes in their work environment, a questionnaire was completed. Number of
particles, relative humidity and temperature were also recorded in a nearby office, equipped with an identical air
processor, where no interventions were made. The results from the first intervention ŽStage 1., comparing number of
airborne particles outdoors to indoors, gave a 19% reduction for PM3 and a 67% reduction for PM7 ŽP 0.001.. The
reduction in PM3 was inconsistent and not statistically significant ŽP 0.3.. The reduction in PM7 from outdoors
and the removal of PM7 created indoors was achieved by optimizing the existing air moving equipment. The results
from the second intervention ŽStage 2 with EAC units installed. comparing indoor to outdoor values, gave a
further reduction in PM3 of 21% ŽP 0.001. and a further 3% reduction for PM7 ŽP 0.05.. Therefore, at the end
of Stage 2, the total reductions in particles from outdoors to indoors were 40% for PM3 and 70% for PM7
ŽP 0.001.. The Stage 2 results strongly suggest that electrostatic forces, created by the EAC unitŽs. improved the
removal of PM3, with no further significant improvement in the reduction of PM7. The questionnaire indicated an
improvement in the IAQ, as perceived by the employees. The results suggest that the EAC system is effective in
reducing PM3 and thereby improving IAQ in an urban office.