Title of article
Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters
Author/Authors
Chen، Chern-Lin نويسنده , , Hung، Guo-Kiang نويسنده , , Chang، Chih-Chang نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
5
From page
169
To page
173
Abstract
The traditional frequency-shift methods for islanding detection of grid-connected PV inverters-the active frequency drift method and the slip-mode frequency-shift method-become ineffective under certain paralleled RLC loads. The automatic phase-shift method is proposed in this paper to alleviate this problem. The method is based on the phase shift of the sinusoidal inverter output current. When the utility malfunctions, the phase-shift algorithm keeps the frequency of the inverter terminal voltage deviating until the protection circuit is triggered. Simulation and experiments are performed for verification.
Keywords
porous media , Volume-average , Interface , Turbulence modeling , Time-average , Stress jump
Journal title
IEEE Transactions on Energy Conversion
Serial Year
2003
Journal title
IEEE Transactions on Energy Conversion
Record number
98499