Title of article
Suppression of slot discharges in a cable wound generator
Author/Authors
M.، Touma-Holmberg, نويسنده , , S.، Hjarne, نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
8
From page
458
To page
465
Abstract
This paper presents a detailed mathematical study to calculate the distribution of the voltages and currents developed on the semiconducting layer of the cable having many points of contact with the stator slot wall and an insulating/semiconducting fixation hose. The calculations are verified experimentally on the worldʹs first high-voltage turbo Powerformer installed in Eskilstuna, Sweden, and rated at 136 kV and 42 MVA.
Keywords
Power-aware
Journal title
IEEE Transactions on Energy Conversion
Serial Year
2003
Journal title
IEEE Transactions on Energy Conversion
Record number
98516
Link To Document