DocumentCode :
1002105
Title :
Partial discharge measurement on three-core belted power cables
Author :
Kreuger, F.H.
Author_Institution :
Dept. of Electr. Eng., Delft Univ. of Technol.
Volume :
4
Issue :
2
fYear :
1989
fDate :
4/1/1989 12:00:00 AM
Firstpage :
927
Lastpage :
931
Abstract :
It is shown that the partial discharge (PD) characteristics of three-core belted-type cables determined using single-phase testing techniques may differ greatly from the actual discharge performance of the cable when subjected to three-phase voltage conditions in service. To achieve meaningful results concerning the voltage ratio and the life expectancy of the cable, careful considerations must be given to the way of energizing the cable and PD response characteristics of single-phase test configurations. An example of erroneous single-phase testing techniques is a circuit which gave an error of up to 88% lower discharge level as compared with three-phase detection. A novel technique was developed in which single-phase voltage was applied to one core, the other two cores were earthed, and the sheath was left floating. The PD detection used a coupling capacitor connected to the energized phase
Keywords :
charge measurement; partial discharges; power cables; coupling capacitor; life expectancy; partial discharge measurement; single-phase testing; three-core belted power cables; three-phase; voltage ratio; Cable insulation; Cable shielding; Circuit testing; Coaxial cables; Frequency; Partial discharge measurement; Partial discharges; Power cables; Power measurement; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.25571
Filename :
25571
Link To Document :
بازگشت