Title :
Quieting Substation Equipment
Author_Institution :
Univ. of Michigan Ann Arbor
Abstract :
With the aid of sound measurements made with an analyzing type of sound meter, it has been possible to ascertain the principal sources of noise in an electric power substation in a residential district and to reduce the noise to an unobjectionable level. The principal sources of noise were found to be an outdoor 6,000-kva transformer and the voltage regulators inside building; by replacig the noisy transformer with a quieter one and replacing the ventilating louvers in the regulator rooms with steel plates the noise on neighboring properties was reduced to about 4 per cent of its original loudness.
Keywords :
Acoustic measurements; Acoustic noise; Noise measurement; Noise reduction; Power measurement; Remuneration; Substations;
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
DOI :