Abstract
Transient voltage distribution characteristics of a hybrid interrupter module have been examined using an experimental model of a hybrid breaker. Tests were conducted to study the voltage distribution between the SF6 gas and the vacuum interrupters immediately after a long current interruption. It is found that the voltage distribution is determined by the resistive impedances of respective interrupters during the post arc current flow and by the capacitive impedances of the interrupter´s contact gaps after the post arc current diminishes
Keywords
circuit breakers; gaseous insulation; sulphur compounds; transients; vacuum apparatus; AC current interruption; SF6 gas interrupters; capacitive impedances; contact gaps; post arc current flow; resistive impedances; transient voltage distribution characteristics; vacuum interrupters; Breakdown voltage; Capacitance; Circuit breakers; Circuit faults; Contact resistance; Cooling; Electric resistance; Equations; Impedance; Interrupters; TV; Testing; Voltage;