Abstract :
A method is introduced for testing insulators under icing conditions. The method is based on and developed from those described in the standard of IEC60-1, IEC 60507 and IEEE Task Force on Insulator Icing Test Methods, which give instructions to test insulators under pollution. Then, the paper explores the effects of various factors, including ice thickness, pollution severity on the surface of insulators before ice accretion, atmospheric pressure, and shed profiles, on the flashover performance of short samples of two different types of silicone rubber (SIR) composite long rod insulators intended for ultra high voltage (UHV) ac transmission lines. The experiments were carried out in the multi-function artificial climate chamber in the High Voltage and Insulation Technological Laboratory of Chongqing University, China. The experimental results reveal the regularity of the effects of ice thickness, pollution severity and atmospheric pressure on the average flashover voltage of two types of composite insulators. Those can provide reference for the outdoor insulation design for UHV ac transmission lines.
Keywords :
composite insulators; flashover; freezing; ice; insulator testing; power transmission lines; China; Chongqing University; High Voltage and Insulation Technological Laboratory; IEC 60507; IEC60-1; IEEE task force; artificial climate chamber; atmospheric pressure; flashover voltage; ice thickness; ice-covered composite insulators; insulator icing test methods; insulator testing; outdoor insulation design; pollution severity; pre-contaminated insulators; silicone rubber composite long rod insulators; ultra high voltage AC transmission lines; voltage 1000 kV; Flashover; IEC standards; Ice thickness; Insulation; Insulator testing; Pollution; Standards development; Surface contamination; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2007.4401217
Filename :
4401217
Link To Document :
بازگشت