• DocumentCode
    1008345
  • Title

    Real-Time Sag Monitoring System for High-Voltage Overhead Transmission Lines Based on Power-Line Carrier Signal Behavior

  • Author

    De Villiers, Wernich ; Cloete, Johannes Hendrik ; Wedepohl, L. Martin ; Burger, Arthur

  • Author_Institution
    Stellenbosch Univ., Stellenbosch
  • Volume
    23
  • Issue
    1
  • fYear
    2008
  • Firstpage
    389
  • Lastpage
    395
  • Abstract
    A new method of measuring the change in the average height above ground of horizontal high-voltage overhead transmission-lines (OHTLs) phase conductors is introduced. The new technique, called power-line carrier sag (PLC-SAG) for short, determines average overhead conductor height variations in real time by correlating sag with measured variations in the amplitude of signals propagating between power-line carrier (PLC) stations. The multifrequency PLC-SAG monitoring signals are injected onto the operational PLC system in the 50- to 500-kHz band, but without interfering with the operational integrity of the PLC teleprotection system. The feasibility of the method was examined using the theory of natural modes for multiconductor systems, and tested by extensive field experiments on two horizontal 400-kV lines operated in South Africa by Eskom. It is concluded that the average height of a horizontal OHTL can be tracked accurately for continuous periods by the PLC-SAG technique.
  • Keywords
    power overhead lines; power supply quality; power system measurement; Eskom; South Africa; high-voltage overhead transmission lines; multiconductor systems; operational integrity; overhead conductor height variations; power-line carrier sag; power-line carrier signal behavior; power-line carrier stations; real-time sag monitoring system; teleprotection system; Africa; Conductors; Monitoring; Phase measurement; Power transmission lines; Programmable control; Real time systems; System testing; Transmission line measurements; Transmission lines; Ampacity; modal analysis and cancellation; overhead transmission-lines (OHTL) sag; power-line carrier (PLC) signal attenuation; real-time OHTL average sag monitoring;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.905550
  • Filename