• DocumentCode
    1011365
  • Title

    A System Out of Step and Its Relay Requirements

  • Author

    Crichton, Leslie N.

  • Author_Institution
    Engineer in the meter engineering department of the Westinghouse Electric & Manufacturing Company, Newark, N. J.
  • Volume
    56
  • Issue
    10
  • fYear
    1937
  • Firstpage
    1261
  • Lastpage
    1267
  • Abstract
    This is a study of the current, voltage, and power values throughout a simple transmission system when machines are operating out of step. The investigation was made to determine the proper relay protection for some large frequency changers which supply power to an electrified railroad. The object was to find means for protecting machines that had already fallen out of step or, if possible, to prevent them from falling out due to overload. The treatment of the problem is geometric, probably the easiest method to comprehend. The assumed conditions have been kept as simple as possible, but it is hoped that the method of treatment is complete enough to permit anyone interested in the subject easily to apply it to more complex problems. It is to be particularly observed that the common method of assuming that a system consists of pure reactance leads to errors that are noticeable on 25-cycle systems where the reactance is low. As a by-product of the study of machine protection, it was discovered that the behavior of different types of line-sectionalizing relays under out-of-step conditions can be easily predetermined and proper adjustments made to obtain a more desirable performance of such relays.
  • Keywords
    Frequency; Poles and zeros; Power generation; Power measurement; Power supplies; Power system protection; Protective relaying; Railway electrification; Relays;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1937.5057453
  • Filename
    5057453