Title :
Lightning Protection of 22-Kv Substations
Author_Institution :
Test engineer with the Duquesne Light Company, Pittsburgh, Pa.
Abstract :
This paper outlines laboratory and field tests with a surge generator and cathode-ray oscillograph which led to the co-ordination of insulation and lightning-arrester performance in substations on the 22-kv subtransmission system of the Duquesne Light Company. A basic level of 150 kv for station insulation was selected in 1932, and methods of obtaining this level are presented together with the operating record for five years. The index representing the station equipment faults in per cent of total system faults during thunderstorms has decreased 86 per cent following system-wide improvement programs modernizing insulation and arresters.
Keywords :
Arresters; Electric breakdown; Inductors; Insulation testing; Lightning protection; Substations; Surges; Transformers;
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
DOI :
10.1109/T-AIEE.1938.5057742