DocumentCode :
1016307
Title :
High-frequency reignition current and its influence on electrical durability of circuit breakers associated with shunt-Reactor current switching
Author :
Tanae, Hiroshi ; Matsuzaka, Eiji ; Nishida, Isao ; Matori, Iwao ; Tsukushi, Masanori ; Hirasawa, Kunio
Author_Institution :
Tohoku Electr. Power Co. Inc., Sendai, Japan
Volume :
19
Issue :
3
fYear :
2004
fDate :
7/1/2004 12:00:00 AM
Firstpage :
1105
Lastpage :
1111
Abstract :
Very-high-frequency and high-peak reignition currents were measured in shunt reactor banks rated at 33 kV 40 MVA during breaking operations of a gas circuit breaker (CB). To measure those kinds of high-frequency transients in reactor circuits in service, a noninvasive method of measuring was proposed using Rogowski coils and capacitive coupled antennas. Some combinations of metals in an electrical collector used in CBs tend to get severely eroded by the high-frequency reignition currents. The paper also proposes a test circuit that can yield high-frequency reignition currents to evaluate the electrical durability of CBs.
Keywords :
electric current measurement; frequency measurement; gas blast circuit breakers; reactors (electric); switching transients; 33 kV; 40 MVA; Rogowski coils; capacitive coupled antennas; circuit breakers; electrical durability; high-frequency reignition current; high-frequency transient; reactor circuit; shunt reactor banks; shunt-reactor current switching; test circuit; Antenna measurements; Circuit breakers; Circuit testing; Current measurement; Electric variables measurement; Frequency measurement; Inductors; Pollution measurement; Shunt (electrical); Switching circuits; Circuit breaker; current collector; electrical durability; reignition; shunt reactor;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.829885
Filename :
1308334
Link To Document :
بازگشت