DocumentCode
1016347
Title
Carrier-Current Losses Measured and Interference Minimized on Boulder-Los Angeles Transmission Lines
Author
Laughlin, J.D. ; Pakala, W.E. ; Reagan, M.E.
Author_Institution
Junior electrical engineer, Bureau of Power and Light, City of Los Angeles, Calif.
Volume
59
Issue
1
fYear
1940
Firstpage
4
Lastpage
10
Abstract
Two unusual facts were disclosed during the field testing of the supervisory-control carrier-current channel on the 287-kv Boulder Dam-Los Angeles transmission lines. Carrier-current losses were much higher than calculations and previous experience had indicated. The interference from power equipment arcs could not be isolated by the use of resonant choke coils, requiring special circuit designs for satisfactory operation.
Keywords
Circuit testing; Coils; Distributed parameter circuits; Inductors; Interference; Loss measurement; Power transmission lines; Propagation losses; Resonance; Transmission line measurements;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1940.5057998
Filename
5057998