Problems of voltage transducer in harmonic measurement
Author :
Xiao, Yao ; Fu, Jun ; Hu, Bin ; Li, Xiaoping ; Deng, Chunnian
Author_Institution :
Hubei Electr. Power Testing & Res. Inst., Wuhan, Taiwan
Volume :
19
Issue :
3
fYear :
2004
fDate :
7/1/2004 12:00:00 AM
Firstpage :
1483
Lastpage :
1487
Abstract :
If the neutral point either on primary or secondary side of potential transformer is not grounded directly, the harmonic voltage measurement will not reflect the real distortion of the system voltage. Also, capacitive voltage transformer on high and medium voltage system cannot be used for harmonic voltage measurement. A new method to set the voltage signal from the tap of Current Transformer bushing is recommended here. The recommended method can achieve a more precise result of harmonic voltage measurement.
Keywords :
bushings; potential transformers; transducers; voltage measurement; current transformer bushing; harmonic measurement; harmonic voltage; potential transformer; voltage transducer; Current transformers; Frequency; Grounding; Insulators; Magnetic resonance; Power system harmonics; Resistors; Transducers; Voltage measurement; Voltage transformers; Capacitive voltage transformer; harmonic measurement; potential transformer; power system harmonics; voltage transducer;