• DocumentCode
    1017626
  • Title

    Bushing Tests

  • Author

    Brownlee, A.L. ; Wickham, W.H.

  • Author_Institution
    Meter engineer, Electrical measurements, with Commonwealth Edison Company. Chicago. Ill.
  • Volume
    60
  • Issue
    10
  • fYear
    1941
  • Firstpage
    940
  • Lastpage
    942
  • Abstract
    The value of power-factor tests on bushings at higher voltages has been demonstrated. Tests at low voltages, while valuable, are inadequate. The power-factor and capacitance vs. voltage characteristics at voltages up to or above the operating voltage are important in judging the condition of the insulation. The nature of bushing deterioration and the significance of high power factor have been shown by laboratory examinations. The findings help to establish a basis for power-factor limits, and for improvements in design and maintenance.
  • Keywords
    Capacitance; Corona; Flanges; Insulation testing; Insulators; Ionization; Laboratories; Life testing; Reactive power; Voltage;