DocumentCode
1017626
Title
Bushing Tests
Author
Brownlee, A.L. ; Wickham, W.H.
Author_Institution
Meter engineer, Electrical measurements, with Commonwealth Edison Company. Chicago. Ill.
Volume
60
Issue
10
fYear
1941
Firstpage
940
Lastpage
942
Abstract
The value of power-factor tests on bushings at higher voltages has been demonstrated. Tests at low voltages, while valuable, are inadequate. The power-factor and capacitance vs. voltage characteristics at voltages up to or above the operating voltage are important in judging the condition of the insulation. The nature of bushing deterioration and the significance of high power factor have been shown by laboratory examinations. The findings help to establish a basis for power-factor limits, and for improvements in design and maintenance.
Keywords
Capacitance; Corona; Flanges; Insulation testing; Insulators; Ionization; Laboratories; Life testing; Reactive power; Voltage;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1941.5058206