DocumentCode
1018472
Title
The Audio Noise of Transformers
Author
Sealey, W.C.
Author_Institution
Electrical engineer in the transformer division of the Allis-Chalmers Manufacturing Company, Milwaukee, Wis.
Volume
60
Issue
3
fYear
1941
fDate
3/1/1941 12:00:00 AM
Firstpage
109
Lastpage
112
Abstract
When transformers arc installed near inhabited districts, their noise must be limited to unobjectionable values. Consequently, means of predetermining noise levels from the desin constants of the transformer and means of noise reduction become necessary. It has been determined that the audio noise of transformers originates in the change in dimensions (magnetostriction) produced in the core steel by the alternating magnetic flux. The vibration caused by the change in dimensions is transmitted to the air through the tank walls. The basic noise may be increased due to the resonant vibration of mechanical parts. Theoretical relations for the sound produced have been derived. These relations are checked by tests on commercial transformers.
Keywords
Acoustic noise; Magnetic cores; Magnetic flux; Magnetic noise; Magnetostriction; Noise level; Noise reduction; Steel; Transformer cores; Vibrations;