The Protective Link
Author
Hodnette, J.K. ; Leonard, M.G.
Author_Institution
Manager of transformer engineering department, Westinghouse Electric and Manufacturing Company, Sharon, Pa.
Volume
60
Issue
5
fYear
1941
fDate
5/1/1941 12:00:00 AM
Firstpage
226
Lastpage
229
Abstract
The protective link is a device recently developed for internal mounting in transformer of a wide variety of types and ratings. Its most common application, however, is in distribution transformers where it serves to disconnect the transformer in case of internal fault. Its action in arc extinction depends on a number of factors including a novel arrangement of the lower terminal which allows it to be expelled from the link when heavy currents are interrupted. Although simple and compact, the link is a very efficient arc-quenching device, and has a remarkably high-circuit interrupting capacity combined with high speed of operation. Power arcs of more than 250,000-kva single phase have been interrupted in one-half cycle.
Keywords
Assembly; Circuit breakers; Circuit faults; Coils; Lamps; Oil insulation; Power transformer insulation; Substation protection; Switches; Transformer cores;