Abstract :
Contamination of paper tapes by corrosive sulfur in insulating oils may cause shorting faults between turns. Typically, this occurs at higher temperature in the upper portions of the windings of shunt reactors and power transformers. In many of the tested oils, high amounts of dibenzyl-disulfide (DBDS) were found.
Keywords :
power transformer insulation; reactors (electric); sulphur; transformer oil; S; corrosive sulfur; dibenzyl-disulfide; insulating oils; paper tapes; power apparatus failures; power transformers; shunt reactors; Copper; Fault detection; Helium; Minerals; Ocean temperature; Oil insulation; Petroleum; Power transformer insulation; Strips; Testing; Oil insulation; standardization; transformers;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :