DocumentCode
1021261
Title
Emergency Overloads for Oil-Insulated Transformers
Author
Vogel, F.J. ; Sloat, T.K.
Author_Institution
Consulting engineer of the Westinghouse Electric and Manufacturing Company, Sharon, Pa.
Volume
61
Issue
9
fYear
1942
Firstpage
669
Lastpage
673
Abstract
New data on the rate of deterioration of cellulose insulation at different temperatures have been obtained. From them a table of time periods and temperatures has been made at which oil-insulated transformers may be operated in order that specific cellulose insulation strengths of approximately 65 per cent of the original value may be maintained. It is expected that this value will be maintained even after operation of a considerable length of time at 105 degrees centigrade.
Keywords
Atmosphere; Dielectrics and electrical insulation; Electrical equipment industry; Oil insulation; Oxidation; Petroleum; Power transformer insulation; Protection; Temperature; Thermal decomposition;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1942.5058587
Filename
5058587