Abstract
Loading of closed delta banks of substation transformers to a point approaching safe thermal limit results in severe over-loading of two transformers as well as decided unbalance in voltage and current when operated in open delta as a result of the failure of one transformer. By the use of mobile capacitor units with capacitors arranged in two unequal groups, the load on two transformers in open delta is reduced, regulation improved, voltage and current are balanced within operating limits, and with the aid of fans, the top oil temperatures¿and consequently, the copper temperatures¿are kept within safe limits. This permits proper loading of transformers in closed delta, a relatively short interruption to service or reduction in load upon failure of one transformer in a bank, and a reduction in number of transformers required for emergency use.
Keywords
Antenna arrays; Capacitors; Directional antennas; Directive antennas; Equations; Phased arrays; Substations; Thermal loading; Transformers; Voltage;