DocumentCode :
1022631
Title :
A Capacitance Bridge for Determining the Ratio and Phase Angle of Potential Transformers
Author :
Bousman, H.W. ; Broeck, R.L.Ten
Author_Institution :
General engineering laboratory, General Electric Company, Schenectady, N. Y.
Volume :
62
Issue :
8
fYear :
1943
Firstpage :
541
Lastpage :
545
Abstract :
A capacitance bridge for the calibration of instrument potential transformers up to 300 kv is presented in this paper. This bridge provides measurements which are correct within 0.1 per cent on ratio and 3 minutes on phase angle. There are within the bridge arrangements for testing its accuracy as determined by the stability of its component arms. It is particularly desirable to have this means of self-testing if transformers are to be tested in a laboratory which does not have extensive standardizing facilities. Further advantages beyond accuracy for standardization purposes are flexibility and ease of operation for production testing, and low cost and small volume as compared to a high-voltage resistance potentiometer.
Keywords :
Arm; Bridge circuits; Built-in self-test; Calibration; Capacitance; Instruments; Phase measurement; Stability; Testing; Voltage transformers;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1943.5058740
Filename :
5058740
Link To Document :
بازگشت