• DocumentCode
    1023187
  • Title

    Magnetic fields from transmission lines: comparison of calculations and measurements

  • Author

    Swanson, J.

  • Author_Institution
    Technol. & Sci. Labs., Nat. Grid Res. & Dev. Centre, Leatherhead, UK
  • Volume
    142
  • Issue
    5
  • fYear
    1995
  • fDate
    9/1/1995 12:00:00 AM
  • Firstpage
    481
  • Lastpage
    486
  • Abstract
    An experiment has been performed to compare the calculated and measured magnetic fields produced by a double-circuit 400 kV power transmission line. The phase currents were measured in the substation at one end of the line, taking particular care to measure the zero-sequence currents accurately, and the earth-wire current was measured at the span where the experiment was conducted. These currents were used to calculate the magnetic fields, using a number of computer programs based on Ampere´s law. The magnetic field was measured at 22 positions ranging from 100 m on one side of the line to 500 m on the other side. Measured and calculated fields generally agreed well. The largest errors were ±7%±1 nT. These errors are attributed to a mixture of random errors in the calibration, resolution and synchronisation of the measuring instruments, and systematic errors stemming from the measurement of the zero-sequence currents
  • Keywords
    magnetic field measurement; magnetic fields; power system analysis computing; power system measurement; power transmission lines; 100 m; 400 kV; 500 m; Ampere´s law; calibration; computer simulation; double-circuit power transmission lines; earth-wire current; magnetic fields; measurements; measuring instruments; resolution; synchronisation; systematic errors; zero-sequence currents;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19952045
  • Filename
    470034