DocumentCode
1024820
Title
Current-Transformer Output and Application Charts
Author
Koller, R.
Author_Institution
Test engineer for the Pacific Electric Manufacturing Corporation, San Francisco, Calif.
Volume
63
Issue
8
fYear
1944
Firstpage
573
Lastpage
577
Abstract
The performance of a multiratio current transformer is most simply represented as a function among the admittance vector locus of the core for one turn, the secondary-turn number N, and the secondary impedance Z. If the ratio of N2/Z is used as a variable, extremely simple application charts for ratio correction factor in relation to primary currents result. The ratio N2/Z furthermore is basic in the matching of transformers and burdens for maximum volt-ampere output at given primary current. Methods for computing the optimum volt-ampere output are given, and a chart is derived from which all data for a correct matching can be obtained at once. The usefulness of these methods is explained in connection with various examples such as applied to relaying circuits commonly used.
Keywords
Admittance; Circuits; Current transformers; Error correction; Impedance; Reactive power; Relays; Steel; Technical drawing; Transformer cores;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1944.5058970
Filename
5058970