DocumentCode :
1027436
Title :
Wave impedance of power transmission line at PLC frequencies
Author :
Neri, Rodolfo ; Ramirez, J. ; Tovar, Jose A. ; Sandoval, C.
Author_Institution :
Instituto de Investigaciones Electricas, Morelos, Mexico
Volume :
31
Issue :
4
fYear :
1983
fDate :
7/1/1983 12:00:00 AM
Firstpage :
646
Lastpage :
649
Abstract :
The wave impedance associated with a single conductor power transmission line is discussed. Computed results show that for power line carrier (PLC) frequencies and within the inductive field the magnitudes and phases of the impedance components Z_{r} and Z_{\\theta} approximate, respectively, average values of 60 and 365 \\Omega and -84\\deg and 0\\deg .
Keywords :
Power system communications; Power transmission lines; Wire communications; Conductors; Electric variables measurement; Frequency measurement; Impedance measurement; Magnetic field measurement; Magnetic noise; Power industry; Power systems; Power transmission lines; Programmable control;
fLanguage :
English
Journal_Title :
Antennas and Propagation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-926X
Type :
jour
DOI :
10.1109/TAP.1983.1143105