• DocumentCode
    1027528
  • Title

    Fluted Sheaths for Oil-Filled Pressure Cables

  • Author

    Klein, N. ; Schieber, D.

  • Author_Institution
    Technion, Israel Institute of Technology
  • Volume
    82
  • Issue
    66
  • fYear
    1963
  • fDate
    6/1/1963 12:00:00 AM
  • Firstpage
    335
  • Lastpage
    343
  • Abstract
    Pressure-difference relations are given for the insulation of oil-filled pressure cables with fluted sheaths. Pressure differences are calculated for a 380-kv cable with such a sheath, and results are compared with those in a cable having a smooth sheath. Pressure drops are four times smaller in cables with fluted sheaths than in those having smooth sheaths when the insulation is uniform and by an order of magnitude smaller and when it is sharply graded, having high-density paper at the conductor.
  • Keywords
    Cable insulation; Cities and towns; Communication cables; Conductors; Fluid flow measurement; Oil filled cables; Oil insulation; Petroleum; Pressure measurement; Printing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1963.291361
  • Filename
    4072802