DocumentCode
1027718
Title
Field Measurement of 345-Kv Lightning Arrester Switching Surge Perrormance
Author
Price, W.S. ; McElroy, A.J. ; Smith, H.M. ; Shankle, D.F.
Author_Institution
American Electric Power Service Corporation
Volume
82
Issue
67
fYear
1963
Firstpage
487
Lastpage
500
Abstract
The purpose of this paper is to present lightning arrester switching surge voltages and currents, measured during a field test program on a 345-kv system. Surges were produced by energization of a transformer-terminated line and by ultra-high-speed re-energization (UHSR) of arrester-terminated lines. Arrester-sparkover levels were 1.1 to 1.7 pu (per unit) of arrester rating, and arrester follow-current peaks were 135 to 940 amperes.
Keywords
Analog computers; Arresters; Continuous improvement; Costs; Current measurement; Lightning; Power transformer insulation; Shape; Surge protection; System testing;