Title
How the Switching-Surge Family Affects Line Insulation
Author
Kalb, J.W.
Author_Institution
The Ohio Brass Company
Volume
82
Issue
69
fYear
1963
Firstpage
1024
Lastpage
1033
Abstract
Tests were made at the Barberton, Ohio, outdoor laboratory of The Ohio Brass Company to cover a range of insulator string lengths, tower sizes, and switching-surge wave shapes, and to explore the response of line insulation to these surges. Surge-front durations of about 250¿sec (microseconds) give the lowest flashover voltages. The effect of a preceding trapped line charge (bias voltage) is small but not negligible. Expected field performance under normally adverse conditions is given for line-to-tower insulation and midspan-to-ground gaps. Rod gap studies explain some of the low positive-polarity dry switching-surge flashovers.
Keywords
Flashover; Insulation testing; Insulator testing; Laboratories; Poles and towers; Power transformer insulation; Shape; Surface contamination; Surges; Voltage control;