Interim Report-Minimum Electrical Clearances ror Substations Based on Switching Surge Requirements
Author :
Report, AIEE
Volume :
82
Issue :
69
fYear :
1963
Firstpage :
1072
Lastpage :
1076
Abstract :
A method has been developed for estimating line-to-ground and phase-to-phase clearances to withstand switching surge voltages in substations. Clearances have been calculated for standard system operating voltages through 500 kv with an assumed switching surge magnitude of 2.8 times the maximum line-to-neutral crest voltage. Consideration has been given to the simultaneous occurrence of opposite polarity switching surges on adjacent phases. Clearance values will be verified by testing programs before being recommended for design purposes.
Keywords :
Electrodes; Flashover; Frequency; Safety; Standardization; Substations; Surges; Transient analysis; Voltage control; World Wide Web;