• DocumentCode
    1030054
  • Title

    Full-Scale Tests for the Allegheny Power System 500-kV Tower-Insulation System

  • Author

    Guyker, W.C. ; Hileman, A.R. ; Wittibschlager, J.F.

  • Author_Institution
    West Penn Power Company
  • Issue
    6
  • fYear
    1966
  • fDate
    6/1/1966 12:00:00 AM
  • Firstpage
    614
  • Lastpage
    623
  • Abstract
    Switching surge, impulse, and 60-cycle tests performed on the APS 500-kV tower-insulation system proved the adequacy of the design which consisted of twenty-four53/4 X 10-inch insulators in V-string configuration with an 11-foot 2-inch minimum strike distance. The minimum switching surge withstand voltage is 965 kV. Minimum impulse critical flashover voltage is 1890 kV, and the minimum 60-cycle flashover and withstand voltages are 707 kV and 660 kV rms, respectively. The switching surge test results from the full-scale tower agreed closely with those predicted from simulated tower-insulation tests. The switching surge flashover probability curve tends to follow the equations for a normal cumulative distribution curve to about the 2 to 5 percent probability level, whereas previous test results showed correlation only to the 5 to 10 percent probability level.
  • Keywords
    Flashover; Impulse testing; Insulation; Insulator testing; Performance evaluation; Poles and towers; Power systems; Surges; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1966.291597
  • Filename
    4073089