• DocumentCode
    1030158
  • Title

    Selective Tripping of Low-Voltage Air Circuit Breakers

  • Author

    Deans, William

  • Author_Institution
    Chief engineer for the I-T-E Circuit Breaker Company, Philadelphia, Pa.
  • Volume
    66
  • Issue
    1
  • fYear
    1947
  • Firstpage
    971
  • Lastpage
    976
  • Abstract
    Selective or sequential tripping in low-voltage air circuit breaker application provides for removal from the system of a faulted part only, leaving the rest of the system in operation. Present standard circuit breakers generally are not suitable. Solution of the problem is through direct-acting series tripping means with distinct current-time characteristics in ranges of overcurrent and fault current, with minimum time to complete interruption the objective. This subjects the circuit breaker to the very severe duty of having to carry short-circuit currents for appreciable times, whereas standard circuit breakers have been designed to open instantaneously. Modified standard circuit breakers may be applied to selective tripping, with limitations of application based upon (1) rated interrupting capacity and (2) series trip coil rating. As tests show that modified standard circuit breakers will carry short-circuit current for necessary times, they also may be applied with relay schemes requiring delayed tripping. In systems using cascade or backup arrangements of circuit breakers, little is gained by selective tripping. It is recommended that for a particular installation choice be made between selective tripping and cascade arrangement, according to relative importance of advantages of each.
  • Keywords
    Calibration; Circuit breakers; Circuit faults; Coils; Costs; Delay effects; Fault currents; Low voltage; Relays; Timing;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1947.5059536
  • Filename
    5059536