DocumentCode :
1030230
Title :
Error Adaptive Control Computer for Interconnected Power Systems
Author :
Ross, C.W.
Author_Institution :
Leeds & Northrup Company, Research and Development Center, Systems Analysis Section
Issue :
7
fYear :
1966
fDate :
7/1/1966 12:00:00 AM
Firstpage :
742
Lastpage :
749
Abstract :
The error adaptive control computer (EACC) permits new and different degrees of freedom for automatic control. It is a logic computer which monitors the control error signal and makes logical decisions on how much, if any, control action should be taken depending on the characteristics of the error signal. Control action may be reduced to any judiciously chosen minimum by adjusting the EACC to discriminate against certain classes of disturbance, e.g., statistical, deterministic, and periodic. Fast control action may still be taken for large and/or sustained disturbances. Certain compromises may be necessary when the EACC is used; in particular, the error signal may be slightly increased. However, the EACC tends to hold the integrated error within a specified value by the action of its integrating circuit. The EACC lends itself to execution by either a special-purpose analog device or a digital computer program. An analog version of the EACC has been constructed and tested both in the field and by simulation.
Keywords :
Adaptive control; Automatic control; Computer displays; Computer errors; Error correction; Integrated circuit interconnections; Logic; Power system control; Power system interconnection; Power systems;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1966.291701
Filename :
4073107
Link To Document :
بازگشت