DocumentCode
1030591
Title
Subsynchronous torsional interactions with static VAR compensators-influence of HVDC
Author
Rostamkolai, N. ; Piwko, R.J. ; Larsen, E.V. ; Fisher, D.A. ; Mobarak, M.A. ; Poltras, A.E.
Author_Institution
GE Ind. & Utility Sales, Schenectady, NY, USA
Volume
6
Issue
1
fYear
1991
fDate
2/1/1991 12:00:00 AM
Firstpage
255
Lastpage
261
Abstract
Planning for the installation of a static VAR compensator (SVC) in Chester, Maine, was initiated in 1987. The prespecification subsynchronous torsional interaction (SSTI) studies showed that the SVC might have a negative influence on the stability of torsional modes of vibration of the nearby turbine generators. The parameters influencing the level of SSTI have previously been identified by the authors by using a simple system (1989). This work is extended to power systems containing an HVDC transmission system. The combined effect of SVC and HVDC on turbine-generator SSTI is investigated with the use of a hypothetical system. Simulation plots for the large machines of New Brunswick and Maine are included to quantify the level of interaction with the Chester SVC. Filtering as a mitigation measure is proposed to eliminate the small level of SSTI attributed to the Chester SVC
Keywords
DC power transmission; high-voltage engineering; power systems; static VAr compensators; Chester; HVDC transmission system; Maine; New Brunswick; SSTI; SVC; filtering; power systems; static VAR compensator; subsynchronous torsional interaction; turbine generators; vibration; Control systems; Damping; Frequency; HVDC transmission; Power system simulation; Power system stability; Reactive power; Senior members; Shafts; Static VAr compensators;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.131070
Filename
131070
Link To Document