• DocumentCode
    1030839
  • Title

    Terminating Rubber and Plastic Cables in Contaminated Environments

  • Author

    Lee, Ralph H.

  • Author_Institution
    E.I. du Pont de Nemours and Company, Inc.
  • Issue
    10
  • fYear
    1967
  • Firstpage
    1179
  • Lastpage
    1184
  • Abstract
    For termination of rubber-insulated cable, it has been found practical to simply expose the factory insulation between stress cone and terminal for uncontaminated outdoor locations. In severe contamination exposure, however, the factory insulation surface and conventional tapes have been found susceptible to deterioration from leakage-current, resulting in tracking and subsequent flashover. This difficulty may be reduced or eliminated by applying track-resistant tapes or tubes over the factory insulation at the termination. Teflon FEP fluorocarbon resin shrink-fit tubing, recently developed, resists this tracking approximately 30 times better than previously-used antitracking tape covers.
  • Keywords
    Cable insulation; Flashover; Insulation life; Plastics; Production facilities; Resins; Resists; Rubber; Stress; Surface contamination;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1967.291870
  • Filename
    4073179