DocumentCode :
1030859
Title :
Determination of Equations and Constants for Life Expectancy Studies for Transformers and Similar Apparatus
Author :
Beavers, M.F.
Author_Institution :
General Electric Company
Issue :
10
fYear :
1967
Firstpage :
1192
Lastpage :
1197
Abstract :
When preparing a computer program involving the use of insulation life expectancy data, it is necessary to know the equation for the life expectancy, or loss-of-life vs. temperature relationship. This information is often presented in chart form for which, in many cases, the equation is not given. To those who work closely with the accepted chemical reaction rate theory (Arrhenius relationship) for thermal aging, there is little problem in determining the constants A and B in life (L) vs. temperature (T) charts based on the equation ln L = B/T + A.
Keywords :
Aging; Chemicals; Equations; Insulation life; Power transformer insulation; Printing; Temperature;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1967.291892
Filename :
4073181
Link To Document :
بازگشت