DocumentCode :
1030935
Title :
Mathematical Analysis of Double Line-to-Ground Short Circuit of an Alternator
Author :
Hwang, Hu H.
Author_Institution :
University of Hawaii
Issue :
10
fYear :
1967
Firstpage :
1254
Lastpage :
1257
Abstract :
The performance equations of ac machines referring to the ¿and ßaxes developed in a previous paper[1] are used to study the case of a double line-to-ground short circuit of a salient pole synchronous machine. Significant corrections are offered to the solutions proposed by other authors pertaining to the same case. Mathematical proof is established for such rectifications. As a result, new expressions for armature currents and field current are developed. In addition, decrement factors and a simple formula for X2 are derived.