DocumentCode
1030942
Title
Ferroresonant Overvoltage Control Based on TNA Tests on Three-Phase Delta - Wye Transformer Banks
Author
Hopkinson, Ralph H.
Author_Institution
General Electric Company
Issue
10
fYear
1967
Firstpage
1258
Lastpage
1265
Abstract
Possible ferroresonant overvoltages are shown on delta- wye transformer banks during single-phase switching as a function of transformer size and lateral length. The application guide is based on industry standard voltage criteria. Secondary loading requirements are given. Simple to use equations are given to allow application of test data.
Keywords
Cable shielding; Capacitors; Control systems; Electrical equipment industry; Equations; Ferroresonance; Switching circuits; Testing; Transient analysis; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1967.291902
Filename
4073191
Link To Document