DocumentCode :
1030954
Title :
Analysis of Transmission Tower Potentials During Ground Faults
Author :
Endrenyi, Janos
Author_Institution :
Hydro-Electric Power Commission of Ontario
Issue :
10
fYear :
1967
Firstpage :
1274
Lastpage :
1283
Abstract :
Since ground fault currents in high-voltage systems are on the increase, the hazards associated with transmission tower voltages during ground faults have become of concern. An analytical method is presented to determine these voltages for long and short lines, arbitrary ground network terminations, and any combination of skywires and counterpoise conductors. The proportion in which the fault current is supplied by the line on both sides of the fault location is taken into account, and the effect of fault currents flowing in parallel external circuits is also considered. The touch and step potentials at the faulted tower are determined and an assessment is given of the hazard they may represent. In a numerical example, several measures aimed at reducing this hazard are compared.
Keywords :
Accidents; Circuit faults; Conducting materials; Conductors; Fault currents; Fault location; Hazards; Poles and towers; Power transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1967.291904
Filename :
4073193
Link To Document :
بازگشت