Title :
Staged Tests on the TVA - SCEC 500-kV Interconnection Between Johnsonville and West Memphis
Author :
Newsom, Robert N. ; Nickelson, S.B. ; Toler, Raymond W. ; Merritt, M. Stephens ; Riesch, Harold A. ; Smith, Frank W.
Author_Institution :
Commonwealth Associates, Inc.
Abstract :
A comprehensive series of field tests was made on the Tennessee Valley Authority-South Central Electric Companies´ (TVA-SCEC) 160-mile, 500-kV interconnecting line and associated terminal equipment. The tests included: energizing at controlled points on voltage wave and deenergizing shunt reactor compensated line with transient voltage limiting breaker; switching line and 1200- MVA transformer with a 161-kV transient voltage limiting breaker; applying solid persistent and transient arcing faults to line while carrying load; and high-speed reclosing after fault clearing. High- speed motion pictures were combined with oscillograms to obtain and relate data. The methods, instrumentation, and results are given in this paper.
Keywords :
Inductors; Motion pictures; Power system interconnection; Power system transients; Power transmission lines; Shunt (electrical); Solids; Substations; Testing; Voltage control;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1967.291817